ULiQfor Surge Protective Devices

Surge Protective DevicesE333248
Guide Information
Siemens Industry Inc
3617 Parkway Lane, Peachtree Corners GA 30092
Model(s): TPS3E1110 (e)
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
2480/277AC3Yn/a-2560L-L200055220200
L-N1200320
L-G1200320
N-G1200320
Evaluated to: UL 1449 4th Ed. Rev: 2016-03-17 and CSA C22.2 No. 269.2-13, 2013-06
(e) - Followed by blank or D, and/or J, and/or P, followed by required option 2.
Note - Unless specified otherwise, All models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2009-09-23© 2024 UL Solutions
Last Revised:2021-04-13