Model(s): STXP480Y10(a), STXP480Y10A(a), STXP480Y15(a), STXP480Y15A(a)
Permanently Connected, STXP Series
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
480/277
AC
3Y
n/a
-40
85
L-L
2000
640
20
200
L-N
1200
320
L-G
1200
320
N-G
700
150