ULiQfor Surge Protective Devices

Surge Protective DevicesE210793
Guide Information
Mersen USA Newburyport-Ma L L C
374 MERRIMAC ST, NEWBURYPORT MA 01950-1930
Model(s): STXP480Y10(a), STXP480Y10A(a), STXP480Y15(a), STXP480Y15A(a)
Permanently Connected, STXP Series
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1480/277AC3Yn/a-4085L-L200064020200
L-N1200320
L-G1200320
N-G700150
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08
(a) - May be followed by additional suffixes.
Note - When suffix F, L, N or G is indicated, It may be preceded or followed by numbers and/or additional letters.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2016-03-22© 2024 UL Solutions
Last Revised:2023-01-10