UL
iQ
for Surge Protective Devices
Surge Protective Devices
E319777
Guide Information
DEHN SE
Hans-Dehn-Strasse 1, Neumarkt 92318 DE
Cat No(s): 952 567
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
1CA (4-1)
1500
DC PV
-
n/a
-40
85
DC+-DC-
4000
-
1500
-
10
10
2
DC+-G
4000
-
1500
-
DC--G
4000
-
1500
-
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA Electrical Certification Notice 516/CSA C22.2 No. 8 13
Note 2 -
Suitable for Field and Factory wiring.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2009-11-13
© 2024 UL Solutions
Last Revised:
2021-12-21