UL
iQ
for Surge Protective Devices
Surge Protective Devices
E316636
Guide Information
ABB Inc.
5900 Eastport Blvd, Richmond VA 23231-4459
Model(s): 01265-(w)
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
120/240
AC
1S
n/a
-35
80
L-L
1200
300
20
100
L-N
700
150
L-G
1200
300
N-G
700
150
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15
(w) -
Followed by 21, 22 or 49 (Legacy Joslyn Enclosure Style)
Note -
Unless specified otherwise, All models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2017-09-06
© 2024 UL Solutions
Last Revised:
2023-03-29