ULiQfor Surge Protective Devices

Surge Protective DevicesE319342
Guide Information
DEAN TECHNOLOGY INC
4117 Billy Mitchell Dr, Addison TX 75001
Model(s): HE2120Y12PT2A
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
2208/120AC3YN/A-4075L-L120030010200
L-N700150
L-G700150
N-G700150
Evaluated to: UL 1449 4th Ed. Rev: 2016-03-17 and CSA C22.2 No. 269.2-13, 2013-06
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2018-02-23© 2024 UL Solutions
Last Revised:2018-02-23