UL
iQ
for Surge Protective Devices
Surge Protective Devices
E314042
Guide Information
Schneider Electric USA, Inc.
Schneider Electric, SURGE PROTECTION BUSINESS, 1751 S 4800 W, Salt Lake City UT 84104
Model(s): SSP05XDSE(#5)(h)*
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
2
480
AC
3D
n/a
-25
60
L-L
2000
552
20
200
L-G
1800
552
Evaluated to: UL 1449 4th Ed. Rev: 2017-07-21 and CSA C22.2 No. 269.2-13, 2013-06
(#5) -
Can be10, 15 or 20.
(h) -
Can be blank or A, and/or J, and/or P, and/or R, or S or T or U, or C.
* -
Complementary Listed EMI Filters (FOKY), E314042.
Note -
All models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2018-05-17
© 2023 UL Solutions
Last Revised:
2018-05-18