ULiQfor Surge Protective Devices

Surge Protective DevicesE314042
Guide Information
Schneider Electric USA, Inc.
Schneider Electric, SURGE PROTECTION BUSINESS, 1751 S 4800 W, Salt Lake City UT 84104
Model(s): SSP05XDSE(#5)(h)*
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
2480AC3Dn/a-2560L-L200055220200
L-G1800552
Evaluated to: UL 1449 4th Ed. Rev: 2017-07-21 and CSA C22.2 No. 269.2-13, 2013-06
(#5) - Can be10, 15 or 20.
(h) - Can be blank or A, and/or J, and/or P, and/or R, or S or T or U, or C.
* - Complementary Listed EMI Filters (FOKY), E314042.
Note - All models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2018-05-17© 2023 UL Solutions
Last Revised:2018-05-18