UL
iQ
for Surge Protective Devices
Surge Protective Devices
E313168
Guide Information
BOURNS INC
1200 COLUMBIA AVE, RIVERSIDE CA 92507-2129
Model(s): 1202-120S
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
120
AC
1
n/a
-35
85
L-N
1200
150
10
25
L-G
1800
150
N-G
1000
150
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.1-17, 2017-02
Note -
All model may be suffixed by X, where X may be blank, A thru Z or 0 thru 9.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2018-07-31
© 2025 UL Solutions
Last Revised:
2024-04-02