ULiQfor Surge Protective Devices

Surge Protective DevicesE320116
Guide Information
LITTELFUSE INC
8755 W Higgins Rd, Suite 500, Chicago IL 60631
Cat No(s): SPD2-480-2P0-R (h)
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)

Notes
1CA (4-1)400AC1N/A-3585L-N3000-960-202001
L-G1500-480-
N-G1500-480-
Evaluated to: UL 1449 4th Ed. Rev: 2017-07-21 and CSA C22.2 No. 269.4-17, 2017-03
(h) - May be followed by additional suffixes
Note 1 - Suitable for Factory wiring only.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2018-10-31© 2024 UL Solutions
Last Revised:2020-09-24