ULiQfor Surge Protective Devices

Surge Protective DevicesE326289
Guide Information
Citel America Inc
10108 USA Today Way, Miramar FL 33025
Model(s): MS100-120T(e), MS80-120T(e), MP100-120T(e), MP80-120T(e)
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
2120/240AC1S--3585L-L100030020200
L-N700150
L-G700150
N-G700150
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.2-17, 2017-02
(e) - may be followed by "-C", may be followed by "-H" or "-L" (C may be combined with H or L)
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.