UL
iQ
for Surge Protective Devices
Surge Protective Devices
E326289
Guide Information
Citel America Inc
10108 USA Today Way, Miramar FL 33025
Model(s): MS100-347Y(e), MS80-347Y(e), MP100-347Y(e), MP80-347Y(e)
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
347/600
AC
3Y
-
-35
85
L-L
3000
1100
20
200
L-N
1800
550
L-G
1800
550
N-G
1800
550
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15
(e) -
may be followed by "-C", may be followed by "-H" or "-L" (C may be combined with H or L)
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2019-07-26
© 2024 UL Solutions
Last Revised:
2024-12-18