UL
iQ
for Surge Protective Devices
Surge Protective Devices
E326289
Guide Information
Citel America Inc
10108 USA Today Way, Miramar FL 33025
Cat No(s): DS50PVS-1500/51
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
4CA
1500
DC PV
-
n/a
-40
75
DC+-DC-
-
5340
1500
n/a
10
n/a
1
DC+-G
-
5380
1500
n/a
DC--G
-
5380
1500
n/a
4CA
1500
DC
-
n/a
-40
85
DC+-DC-
-
5120
1500
n/a
10
n/a
1
DC+-G
-
5220
1500
n/a
DC--G
-
5220
1500
n/a
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08
Note 1 -
Suitable for Factory wiring only.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2015-04-30
© 2023 UL Solutions
Last Revised:
2023-02-23