ULiQfor Surge Protective Devices

Surge Protective DevicesE322885
Guide Information
ABB FRANCE
Activite Pole Foudre Soule & Helita, 1 Ave Des Victimes Du 11 Juin 44, Boite Postale 303, Bagneres-De-Bigorre 65203 FR
Cat No(s): OVR T2 3N 40-320 P TS U
Series OVR T2
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)

Notes
4CA (5)480/277AC3Yn/a060L-L-5880640102020n/a1
L-N-2940320510
L-G-82505751110
N-G-5310255600
Evaluated to: UL 1449 4th Ed. Rev: 2018-08-01 and CSA C22.2 No. 269.5-17, 2017-09
Note 1 - Suitable for Factory wiring only.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2011-03-12© 2021 UL LLC
Last Revised:2020-02-06