UL
iQ
for Surge Protective Devices
Surge Protective Devices
E514545
Guide Information
SCHNEIDER ELECTRIC INDUSTRIES SAS
ELECTROPOLE/EYBENS, POWER / FD, 31 RUE PIERRE MENDES FRANCE, GRENOBLE CEDEX 9 38050 FR
Cat No(s): M9L13208
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)
Notes
1CA (4-1)
208/120
AC
3Y
n/a
-40
85
L-L
1200
-
350
-
20
200
2
L-N
600
-
175
-
Evaluated to: UL 1449 4th Ed. Rev: 2018-08-01 and CSA C22.2 No. 269.4-17, 2017-03
Note 2 -
Suitable for Field and Factory wiring.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.