ULiQfor Surge Protective Devices

Surge Protective DevicesE330181
Guide Information
PHOENIX CONTACT GmbH & Co. KG
Flachsmarktstrasse 8, Blomberg 32825 DE
Model(s): BXT-4XP-SEC-T3-120
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
2120AC120-4080L-N700150510
L-G1000150
N-G900150
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.2-17, 2017-02
Note - All Cat. Nos. may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2020-05-05© 2024 UL Solutions
Last Revised:2023-08-23