ULiQfor Surge Protective Devices

Surge Protective DevicesE335146
Guide Information
APPLETON GROUP
9377 W HIGGINS RD, ROSEMONT IL 60018
Cat No(s): STFE200-10N (e)
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MLV
(Vpk)
MCOV
(V)
Vn
(Vdc)
In
(kA)
SCCR
(kA)

Notes
2CA (4-2)120AC120-4025L-N400-150-352,4
L-G500-150-
N-G500-150-
Evaluated to: UL 1449 4th Ed. Rev: 2018-08-01 and CSA C22.2 No. 269.4-17, 2017-03
(e) - Complementary Recognition as FOKY2 under File E311348.
Note - All models may be followed by additional suffixes. (numbers and/or letters)
Note 2 - Suitable for Field and Factory wiring.
Note 4 - Series External Overcurrent Protection required, see Electrical Ratings in the Recognition report.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2009-12-15© 2024 UL Solutions
Last Revised:2024-10-16