ULiQfor Surge Protective Devices

Surge Protective DevicesE354261
Guide Information
Weidmueller Interface GmbH & Co. KG
Klingenbergstrasse 26, Detmold 32758 DE
Model(s): VPU AC II US 2 240/50
Open-Type SPD
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1240AC1n/a-4085L-N180060020150
L-G900300
N-G900300
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA C22.2 No. 269.1-17, 2017-02
Note - All models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2020-06-19© 2024 UL Solutions
Last Revised:2021-10-19