UL
iQ
for Surge Protective Devices
Surge Protective Devices
E210793
Guide Information
Mersen USA Newburyport-Ma L L C
374 MERRIMAC ST, NEWBURYPORT MA 01950-1930
Model(s): STP208YN07, STP208YN07M
Open-Type SPD, STP Series
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
120/208
AC
3Y
n/a
-40
85
L-L
1200
350
20
200
L-N
600
175
L-G
1200
175
N-G
600
175
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA C22.2 No. 269.1-17, 2017-02
Note -
When suffix F, L, N or G is indicated, It may be preceded or followed by numbers and/or additional letters.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2020-12-30
© 2024 UL Solutions
Last Revised:
2023-01-10