ULiQfor Surge Protective Devices

Surge Protective DevicesE319871
Guide Information
PROSURGE ELECTRONICS CO LTD
Building 27, Phase 2, Liando U Valley, Jiansha Road, Danzao, Nanhai, Foshan Guangdong 528216 CN
Model(s): PSPE480D11/T1
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1480AC3DN/A-4080L-L400055010200
L-G1800550
Evaluated to: UL 1449 5th Ed. Rev: 2022-12-15 and CSA C22.2 No. 269.1-17, 2017-02
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2017-10-03© 2024 UL Solutions
Last Revised:2024-04-30