UL
iQ
for Surge Protective Devices
Surge Protective Devices
E333248
Guide Information
Siemens Industry Inc
3617 Parkway Lane, Peachtree Corners GA 30092
Model(s): TPS4F03050N
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV
Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)
Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1
480
AC
3D
n/a
-35
85
L-L
2000
550
20
200
L-G
2000
550
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08 and CSA C22.2 No. 269.1-17, 2017-02
Note -
Unless specified otherwise, All models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:
2021-03-24
© 2024 UL Solutions
Last Revised: