ULiQfor Surge Protective Devices

Surge Protective DevicesE316636
Guide Information
ABB Inc.
5900 Eastport Blvd, Richmond VA 23231-4459
Model(s): 1265-49, 1265-49-R, 1265-49-PL1, 1265-49-RB, 1265-49-RBA, OVRHS3U401202P, OVRHS3U402402P5
Permanently Connected
SPD
Type
Volts
(V)
AC/DC
DC PV

Phase
Amps
(A)
Ambient
Min(°C)
Ambient
Max(°C)

Mode
VPR
(Vpk)
MCOV
(V)
In
(kA)
SCCR
(kA)
1240/120AC1Sn/a060L-L100026010100
L-N800150
L-G1000260
N-G800150
Evaluated to: UL 1449 5th Ed. Rev: 2021-01-08
Note - Unless specified otherwise, All models may be followed by additional suffixes.
SPDs investigated for Type 1 applications are automatically suitable for Type 2 applications and may be marked for SPD Type 1 and/or Type 2 applications. SPDs only marked "SPD Type 2" are not suitable for Type 1 applications.
Where a minimum ambient temperature is not specified, assume 0°C unless the product is marked otherwise or with an Outdoor use Environmental Rating. See Electrical Equipment for Use in Ordinary Locations (AALZ) for details regarding Environmental Ratings.
Report Date:2009-10-15© 2024 UL Solutions
Last Revised:2022-12-14